四相架空输电线路的换位与参数研究-【新闻】微调电容器

发布时间:2021-04-20 12:15:39 阅读: 来源:隧道防火涂料厂家

四相架空输电线路的换位与参数研究

分类号:TM63 文献标识码:A

文章编号:2258-8223 23-2276-24STUDY OF TRANSPOSITION AND PARAMETER

OF FOUR-PHASE OVERHEAD TRANSMISSION LINELIU Guang-ye

YANG Yi-han

ABSTRACT:The transposition schemes of arbitrary arrangement four-phase overhead lines are discussed in detail, and the each sequence parameter calculation of the lines are also studied. In this paper, the conception of space electromagnetic field decoupling of square arrangement four-phase overhead lines is extended,it maks the analising very simple and clear. Moreover, the transmisstion power density of four-phase transmission lines are compared with three-phase transmission lines under the same condition of parameters, and the land occupied by four-phase system with unit capacity transmission power, is reduced by 29%~47%, compared with three-phase system.

KEY WORDS:four-phase transmission; overhead transmission line; transmission line transposition ; transmission line parameter▲2 引言在2972年法国举行的第24届国际大电网会议上,美国学者H. C. BARNES与L. D. BARTHOLD首次提出了一个超出常规的输电方案,即采用多于三相的输电线路。其结果是[2]:比三相改进了线路走廊的利用能力,因为在三相系统中,实质上约95%的电能只是在紧挨着金属导体约5%的空气体积中传输;可以明显地减小导线的电位梯度;更好地利用空气作为绝缘介质。此后,多相输电作为一种提高输送功率密度的重要方法,引起了众多电力研究者的重视[2~4]。进一步的研究与试验显示,多相输电线路运行的可闻噪声、无线电噪声、地面电磁场等环境指标均优于三相线路[5,6]。

在研究三相变四相电力变压器[7,8]的基础上,曾首次论述了四相输电系统的基本特性[9]。四相输电方式的主要优点是:增加一相线路,空间电磁场分布更加均匀,输送容量增加,线路走廊反而减小,能提高线路的输送功率密度,节省输送单位容量的投资成本;四相线路是偶数相,对称性好,四相导线可以对称地悬挂在单柱杆塔的两侧,杆塔结构简单;四相线路可以采用两相邻相运行,可以提高输电系统运行的可靠性与暂态稳定性;四相输电线路故障的组合类型远远少于六相及以上多相输电线路,不会给故障分析、继电保护的设计与整定增加太大的困难。